SIDEWALL SPRINKLER EXTENDED COVERAGE

SIDEWALL SPRINKLER EXTENDED COVERAGE

MODEL: SD1125

The Model A SD1125 ½”orifice, extended coverage horizontal sidewall sprinkler is designed for extended coverage or recessed installation. The design provides a crescent-shaped water discharge pattern for installation along a wall or under a beam or ceiling. The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (quick response) for prompt, precise operation. The die cast frame is more streamlined and attractive than traditional sand cast frames.

It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various temperature ratings and finishes to meet many design requirements. The recessed pendent should be utilized with a Model A recessed escutcheon which provides up ½” of adjustments.

SPECIFICATIONS

SPRINKLER IDENTIFICATION NUMBER

Quick Response SD1125(bulb 3mm)

STYLE

Horizontal Sidewall

FINISH

Natural/Chrome

K FACTOR

5.6Imp.(80S.I)

RESPONSE TIME INDEX (RTI)

Quick Response 30

NOMINAL THREAD SIZE

½”NPT(15mm)

MAX. WORKING PRESSURE

175PSI(1200kPa)

FACTORY HYDROSTATIC TEST

100%@500PSI(3450 kPa)

MIN. OPERATION PRESSURE

7 PSI (48 kPa)

Back